Title : ( A New Single Ended Fault Location algorithm for Combined Transmission Line Considering Fault Clearing Transients without Using Line Parameters )
Authors: ismail niazi , Javad Sadeh , Ebrahim Niazy ,Abstract
This paper presents a new single ended fault location method for underground cable combined with overhead line that uses fault clearing transients instead of fault-generated transients without utilizing line parameters. Applying wavelet transform on voltage samples taken from the sending end of the cable, first, second and third inceptions of traveling waves to the fault locator are detected and faulty section is determined. Then, exact location of fault is calculated. Single-ended algorithm, does not need to the communication system and GPS. Accuracy of algorithm is not affected by aging, climate and temperature variations, which change the wave speed. Fault resistance, fault inception angle and fault distance does not affect accuracy of algorithm. Extensive simulations carried out using SimPowerSystem toolbox of MATLAB software, confirm the capabilities and high accuracy of the proposed method to find the location of fault under different system and fault conditions.
Keywords
, Fault location, fault clearing transients, combined lines, wavelet transform, wave speed@inproceedings{paperid:1018669,
author = {Niazi, Ismail and Sadeh, Javad and Ebrahim Niazy},
title = {A New Single Ended Fault Location algorithm for Combined Transmission Line Considering Fault Clearing Transients without Using Line Parameters},
booktitle = {25th Power System Conference-PSC2009},
year = {2010},
location = {تهران, IRAN},
keywords = {Fault location; fault clearing transients;
combined lines; wavelet transform; wave speed},
}
%0 Conference Proceedings
%T A New Single Ended Fault Location algorithm for Combined Transmission Line Considering Fault Clearing Transients without Using Line Parameters
%A Niazi, Ismail
%A Sadeh, Javad
%A Ebrahim Niazy
%J 25th Power System Conference-PSC2009
%D 2010