Title : ( Optimal Placement and Sizing the Multi-Criteria of Fault Current Limiters in Presence of Distributed Generation in Sub-transmission )
Authors: Mohammad Fathi Sheikh Ahmad , Javad Sadeh ,Access to full-text not allowed by authors
Abstract
This paper proposes multi-criteria optimization method for finding optimal number, places and sizes of FCL simultaneously to decrease short circuit currents under allowable values of protective devices. In fact this paper takes the tradeoff between minimization of operation time of overcurrent relays, minimization of FCL's impedance amplitude and reset to zero of the number of mis-coordination of overcurrent relays in the network. Sensitivity analysis is performed to reduce the searching space for optimal placement and optimal sizing multi-criteria of the FCL. Optimal number, size of impedance and optimal location of FCL are selected to solve the most protective problems due to usage of distributed generation in the network. Finally, the best exploitation of FCL will be obtained.
Keywords
Fault current limiter (FCL); distributed generation (DG); optimal placement; optimal sizing;@inproceedings{paperid:1055349,
author = {Fathi Sheikh Ahmad, Mohammad and Sadeh, Javad},
title = {Optimal Placement and Sizing the Multi-Criteria of Fault Current Limiters in Presence of Distributed Generation in Sub-transmission},
booktitle = {4th Iranian Conferenec on Renewable Energy & Distributed Generation},
year = {2016},
location = {مشهد, IRAN},
keywords = {Fault current limiter (FCL); distributed generation
(DG); optimal placement; optimal sizing;},
}
%0 Conference Proceedings
%T Optimal Placement and Sizing the Multi-Criteria of Fault Current Limiters in Presence of Distributed Generation in Sub-transmission
%A Fathi Sheikh Ahmad, Mohammad
%A Sadeh, Javad
%J 4th Iranian Conferenec on Renewable Energy & Distributed Generation
%D 2016